Internal Electrical Work -Abstract of CPWD
Circuits: Topic Abstracts Lighting Circuit Per Circuit Not more than 10 Points of Lighting or Total 800Watt which is less Power Circuit For Residential Per Circuit Less than 2 No of 5A/15A Plug Socket Power Circuit For Non Residential Per Circuit Less than 1 No of 5A/15A Plug Socket Plug Socket In Residential wiring ,wiring of Socket outlet shall be done by copper Cable only Min Size of Wire For Lighting Circuit Smallest size of conductor shall be 1.5 Sq.mm Min Size of Wire For Power Circuit Smallest size of conductor shall be 4 Sq.mm Plug Socket Plug Socket 5A/6A or 15A/16A Socket shall be installed at following heights: =For Non Residential building 23cm above floor =For Kitchen 23cm above Platform. =For Bathroom not Socket is p...